Low Voltage Input /Output Vigilon Interface Module can be used to control a resistive load of up to 1A at 30Vdc/ac via a set of single pole change over contacts. In addition there is an input to allow the monitoring of the external equipment. In this application the input must be configured as a confirmation input. A confirmation input generates a fault if a change of state is not seen within the predefined period of a specific output. The S4 interface modules can be mounted in other equipment housings using the DIN rail mount brackets. A module can also be fitted into a plastic box or metal box.Features & Benefits:Analogue addressable communicationsBuilt-in type identification automatically identifies these devices to the control panelReliable communication technique with high noise immunitySoft or SAFE addressingLoop Powered devices reducing cost of installation and maintenanceOptions to connect conventional fire detectors such as flame and beam detectorsCommon mounting options including surface mount, panel mount and DIN rail mountDual-colour LEDsPlug-in terminal connections for ease of wiringCertifications:CELPCBEN54-17:2005EN54-18:2005